Measure Transients for Damage Control
With SATEC’s ALL IN ONE Revenue Meter, Power Quality Analyzer & Fast Transient Recorder |
Transient overvoltages occur as a result of lightning, faults in power networks or reactive loads switching, causing severe damages to equipment. According to the EN50160 standard definition, transient overvoltage is a short duration oscillatory or non-oscillatory overvoltage usually highly damped and with a duration of a few milliseconds or less. Due to the short duration of these events, they can only be detected by special, fast measurement and recording.
The Problem
Global damages due to transient overvoltages are estimated at billions of dollars annually. These disturbances cause serious damage to equipment, such as transformers, capacitors and computers, and result in financial losses for factories and business activities, as well as to customers.
Damage to Customers & Equipment
Causes of Transient Overvoltages
|
|
|
Measuring ProblemsThe duration of transient overvoltages is very short, from microseconds to 10msec, and the amplitude of the peaks is high. Standard Revenue and Power Meters are unable to measure and record these transients.
|
||
Revolutionary Device for a Smart Solution |
||
|
With the new EM720T eXpertmeter™, SATEC is now able to offer a solution to the deadly problems caused by transient overvoltages. |
|
|
Transient Overvoltages Recorded by EM720T
Transient overvoltages are detected as impulse according to next parameters—impulse amplitude, duration and rise time. In the EM720, minimal impulse amplitude is set by the consumer. The impulse amplitude is referenced to the nominal voltage amplitude (1.414 Un), and should be set at 30% or more. The impulse duration may be from 20 microsecond up to 10 ms.

Figure 1. OMICRON Signal Generator waveforms
Figure 1 shows a waveform generated by OMICRON and recorded by EM720. The waveform has an impulse of 1 ms and an amplitude of 100%. In this experiment, voltage neutral input was connected to ground input of the EM720.

Figure 2. SATEC Signal Generator waveforms
Figure 2 shows a waveform generated by a special device.
The waveform has an impulse of 88 microsecond and an amplitude of 410%.

Figure 3. Transient overvoltage in a 400V network
The waveform in figure 3 was recorded by EM720. The instrument
was installed in a 400V network. The Impulse has a duration of 22 microseconds and an amplitude of 378.9V (phase to ground).

Figure 4. Transient overvoltage with equipment damage
Figure 4 shows amplitude in phase 1—720.4V (phase to ground).
Amplitude in neutral—369.6 (phase to ground). In the case illustrated here, damages were caused to electronic equipment.
Figure 5. Power Quality Event Log
Figure 5 lists transient overvoltage events recorded in PQ Log.





