The EDL180 is a portable version of the Class A (Edition 3) PM180 power quality analyzer, which holds extensive track record serving as the platform for power quality monitoring systems in worldwide national grids.
Equipped with a 24V battery for backup power supply and flexible current clamps, it is fitted in a lightweight traveling bag for convenient handling
Power Quality
Backup Battery Power
Built-in UPS providing over 4 hours of work at maximum consumption
Communication
3V AC Current Inputs
Supplied with current clamps
Voltage Inputs: 690V AC nominal
Nominal voltage: 690V AC
Operating range: up to 828V AC
5th AC/DC voltage input:
up to 300V DC (monitoring substation battery)
Built-in:
Optional/additional: (1 per device):
Graphic color display: 5.7″ touchscreen
Built-in:
For all downloads available for the PM180 analyzer, please go to the Downloads tab on the PM180’s main page.
Transient Recorder Module
Records voltage transients of up to 2kV (L-G) at 1024 samples/cycle per channel
Fault Recorder Module
Additional current input offers separated metering & protection CT connection, records current faults of up to 200A (40*In)
PMU Functionality
Phasor measurement unit (PMU) provides synchrophasor and frequency measurements compliant with the IEEE C37.118.1 P performance class, and real-time cyclic exchange of synchronized phasor data with the substation phasor data concentrator (PDC) based on the IEC 61850-9-2 sampled value (SV) service.
Auxiliary Power Supply
(max. one auxiliary power supply per PM180)
Contact now