>  Home >  Products >  EM720

Hybrid Revenue Meter
& Power Quality Analyzer ( PQA / PQM)

The EM720 is the IEC version of the eXpertMeterTM Series of multifunctional power analyzers. This series was designed to deliver two functionalities that are present in every substation, in a single device:

  • PQ Analyzer & Power Meter, typically required by utility SCADA teams
  • Revenue Meter, typically operated and read by the utility billing department

Combining these functions simplifies design and eliminates redundancy.

Revenue Meter:

  • Class 0.2S per IEC 62053-22
  • Anti-tamper revenue grade design
  • 5A or 1A current inputs

Power Quality Analyzer

  • PQ monitoring per IEC 61000-4-30 Class A requirements
  • EN50160 / GOST 32144 statistics and reports
  • Waveform capture and transient recording at 1024 samples per cycle

Transformer and transmission line losses calculation

Communication

  • IEC 61850
  • Interfaces: RS485/232; ETH; 2G/3G; USB; IR / IRIG-B
  • Open protocol: Modbus RTU; DNP3.0

Digital & Analog I/O: up to 8 I/O

Backup Battery: up to 6 hours of full operation. Rechargeable

Transformer/Line losses calculation

Based on parameters such as copper losses and iron losses, this unique economical feature enables the meter to accurately establish a virtual metering point. This eliminates the need to construct a costly high voltage metering point, requiring a metering cubicle, CT and PT.

Power Meter

  • Voltage, current (including neutral current), power, energy, power factor, frequency, voltage/current unbalance
  • Ampere/Volt demand meter
  • 50/60 Hz measurements
  • 256 samples per cycle

Revenue Meter

  • Class 0.2S accuracy per IEC 62053-22
  • Four-quadrant import and export (e.g. PV), active and reactive energy poly-phase static meter
  • Three-phase total and per phase energy measurements; active, reactive and apparent energy counters
  • Time Of Use (TOU): 10 billing energy and maximum demand registers, 8 tariff rates, 4 seasons x 4 types of days, 8 tariff changes per day
  • Easily programmable tariff calendar schedule
  • Revenue grade, anti-tamper design
  • Virtual metering: transformer and transmission line losses calculation

Power Quality Analyzer

  • Power Quality Analysis according to IEC 61000-4-30 Class A
  • EN50160 / GOST 32144 monitoring, statistics & reports
  • 6 hour battery back-up and/or auxiliary power supply for continuous recording of major dips & interruptions
  • Harmonics & Inter-harmonics per IEC 61000-4-7
  • Voltage and current THD, TDD and K-Factor, up to 50th order harmonic
  • Voltage and current harmonic spectrum and angles
  • Directional power harmonics
  • Flicker measurement per IEC 61000-4-15
  • Waveform recording, up to 1024 samples/cycle*

*with transient recording card

Transient Recorder

  • Records fast transients overvoltages >17 microseconds
  • Transients measured relative to ground
  • Measures up to 2 kV pulses

Current Inputs

1A or 5A inputs

voltage input

Measurement and Power Supply*:

  • High-range power supply (207-480V option):96- 575V AC
  • Low range power supply (100-120V option): 45 – 250 V AC

*self-energized (SE) from voltage inputs

I/O

Built-in:

  • 4 Digital Inputs
  • 1 form A Solid State Relay

Modular I/O (available options):

2 Digital Inputs + 2 digital outputs (Solid State or Electro Mechanical)

(see Module tab for detailed spec)

Programmable Logical Controller

  • Embedded programmable controller
  • 16 control set points; programmable thresholds and delays
  • ½-cycle response time

Communication Interfaces

All communication interfaces (other than IR) are available as add-on modules

Default:

  • Standard 2-wire RS-485 serial port
  • ETH
  • IR (optical)
  • USB

Optional:

  • IRIG-B
  • 4G modem

Communication Protocols

  • IEC 61850
  • IEC 62056-21 (DLMS)
  • Modbus RTU
  • ASCII
  • DNP 3.0
  • Modbus/TCP
  • DNP3/TCP

Meter Security

  • 3 levels Password security for protecting meter setups and accumulated data from unauthorized changes
  • anti-tamper design

Mounting

Wall-mount

Display

  • 99 x 24mm backlit LCD display
  • Auto-scroll option with adjustable page exposition time; auto-return to a default page

Real Time Clock

  • Built-in clock and calendar functions
  • 2 year battery backup
  • SNTP Time Synchronization

Power Supply

Available Options:

Self-energized (default):

  • 45 – 250 V AC
  • 96- 575V AC

Auxiliary power supply (module):

  • 88-265V AC / 90-290V DC
  • 24V DC

Isolation

  • Dielectric withstand: 6 kV impulse, 4 kV AC @ 1min
  • I/O and Com Ports – 4 kV AC

Field Replaceable Hot Swap Modules

img

Auxiliary Power Supply

Auxiliary Power Supply Options
  • 24V DC
  • 88-265V AC / 90-290V DC

Backup Battery

Rechargeable battery (6H of full operation), providing automatic backup in case of an external power failure

I/O Modules

Digital Input/Output—2DI/2DO
  • Form A Relay Output 5A / 250V AC
  • Form A Solid State Relay Output 0.1A / 250V AC

Communication Modules

  • ETH: includes USB + 2nd RS485 port
  • 4G Cellular

Models

EM720: Standard
EM720T: Includes Transient Recorder

Contact now

one of our experts






    Featured Content

    top